712
Data Control Instructions
Section 3-18
When CIO 000000 is ON, the contents of CIO 2005 is scaled using the linear
function defined by
∆
X (0FA0),
∆
Y (0400), and the offset (07D0). These values
are contained in D00100 to D00102, and the result is output to D00200.
3-18-8 SCALING 3: SCL3(487)
Purpose
Converts signed BCD data into signed binary data according to the specified
linear function. An offset can be input in defining the linear function.
Ladder Symbol
Variations
Applicable Program Areas
(
∆
X)
∆
X
∆
Y
P1:
P1+1:
P1+2:
Contents of R (D00200)
Contents of S (CIO 0200)
Offset
Offset
07D0 Hex
0FA0 Hex
0400 (
∆
Y)
P1
R
0
F A
0
D00100
D00101
D00102
S: Source word
P1: First parameter word
R: Result word
SCL3(487)
S
P1
R
Variations
Executed Each Cycle for ON Condition
SCL3(487)
Executed Once for Upward Differentiation
@SCL3(487)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program
areas
Step program
areas
Subroutines
Interrupt tasks
OK
OK
OK
OK