Data Control Instructions
Section 3-18
3-18-6 SCALING: SCL(194)
Purpose
Converts unsigned binary data into unsigned BCD data according to the
specified linear function.
Ladder Symbol
Variations
Applicable Program Areas
Operands
The contents of the four words starting with the first parameter word (P1) are
shown in the following diagram.
Note P1 to P1+3 must be in the same area.
Operand Specifications
S: Source word
P1: First parameter word
R: Result word
SCL(194)
S
P1
R
Variations
Executed Each Cycle for ON Condition
SCL(194)
Executed Once for Upward Differentiation
@SCL(194)
Executed Once for Downward Differentiation Not supported.
Immediate Refreshing Specification
Not supported.
Block program
areas
Step program
areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Scaled value for point A (Ar)
0000 to 9999 (4-digit BCD)
Unscaled value for point B (Bs)
0000 to FFFF (binary)
Scaled value for point B (Br)
0000 to 9999 (4-digit BCD)
Unscaled value for point A (As)
0000 to FFFF (binary)
P1
P1+1
P1+2
P1+3
15
0
15
0
15
0
15
0
Area
S
P1
R
CIO Area
CIO 0000 to CIO
6143
CIO 0000 to CIO
6140
CIO 0000 to CIO
6143
Work Area
W000 to W511
W000 to W508
W000 to W511
Holding Bit Area
H000 to H511
H000 to H508
H000 to H511
Auxiliary Bit Area
A000 to A959
A000 to A956
A448 to A959