218
Timer and Counter Instructions
Section 3-6
Note In CS1 and CJ1 CPU Units, these are turned OFF.
In CS1-H, CJ1-H, CJ1M, and CS1D CPU Units, these Flags are left
unchanged.
Precautions
Timer numbers are shared by the TIM, TIMX(550), TIMH(015), TIMHX(551),
TMHH(540), TMHHX(552), TTIM(087), TTIMX(555), TIMW(813),
TIMWX(816), TMHW(815), and TMHWX(817) instructions. If two timers share
the same timer number, but are not used simultaneously, a duplication error
will be generated when the program is checked, but the timers will operate
normally. Timers which share the same timer number will not operate properly
if they are used simultaneously.
The Completion Flag is updated only when TMHH(540)/TMHHX(552) is exe-
cuted. The Completion Flag can thus be delayed by up to one cycle time from
the actual set value.
The present value of timers programmed with timer numbers 0000 to 2047 will
be updated even when the timer is on standby. The present value of timers
programmed with timer numbers 2048 to 4095 will be held when the timer is
on standby.
Timers will be reset or paused in the following cases. (When a timer is reset,
its PV is reset to the SV and its Completion Flag is turned OFF.)
Note
1.
If the IOM Hold Bit (A50012) has been turned ON, the status of timer Com-
pletion Flags and PVs will be maintained when the operating mode is
changed.
2.
If the IOM Hold Bit (A50012) has been turned ON and the status of the IOM
Hold Bit itself is protected in the PLC Setup, the status of timer Completion
Flags and PVs will be maintained even when the power is interrupted.
3.
The PV will be set to the SV when TMHH(540)/TMHHX(552) is executed.
When an operating TMHH(540)/TMHHX(552) timer is in a jumped program
section (JMP(004), CJMP(510), CJPN(511), JME(005)), the timer’s PV will
continue timing. (See note.) (The jumped TMHH(540)/TMHHX(552) instruc-
tion won’t be executed, but the PV will be refreshed every 1 ms.)
Note With the CS1D CPU Units, the PV will not be refreshed in the above case.
When TMHH(540)/TMHHX(552) is in a program section between IL(002) and
ILC(003) and the program section is interlocked, the PV will be reset to the SV
and the Completion Flag will be turned OFF.
When a TMHH(540)/TMHHX(552) timer is forced set, its Completion Flag will
be turned ON and its PV will be set to 0000. When a TMHH(540)/
TMHHX(552) timer is forced reset, its Completion Flag will be turned OFF and
its PV will be reset to the SV.
Condition
PV
Completion Flag
Operating mode changed from RUN or
MONITOR mode to PROGRAM mode or
vice versa.
1
0000
OFF
Power supply interrupted and reset
2
0000
OFF
Execution of CNR(545)/CNRX(547), the
RESET TIMER/COUNTER instructions
3
BCD: 9999
Binary: FFFF
OFF
Operation in interlocked program section
(IL(002)–ILC(003))
Reset to SV.
OFF
Operation in jumped program section
(JMP(004)–JME(005))
PV continues
decrement-
ing.
Retains previous status.