![Omron CJ1G-CPUxx Instructions Manual Download Page 184](http://html1.mh-extra.com/html/omron/cj1g-cpuxx/cj1g-cpuxx_instructions-manual_742491184.webp)
163
Sequence Input Instructions
Section 3-3
program section, or a subroutine. Refer to 3-5-3 INTERLOCK and INTER-
LOCK CLEAR: IL(002) and ILC(003), 3-5-4 JUMP and JUMP END: JMP(004)
and JME(005), and 3-20 Interrupt Control Instructions for details.
Examples
When CIO 000000 goes from OFF to ON in the following example,
CIO 000001 is turned ON for just one cycle.
3-3-14 BIT TEST: TST(350) and TSTN(351)
Purpose
LD TST(350), AND TST(350), and OR TST(350) are used in the program like
LD, AND, and OR; the execution condition is ON when the specified bit in the
specified word is ON, and OFF when the bit is OFF.
LD TSTN(351), AND TSTN(351), and OR TSTN(351) are used in the program
like LD NOT, AND NOT, and OR NOT; the execution condition is OFF when
the specified bit in the specified word is ON, and ON when the bit is OFF.
Ladder Symbols
Variations
Cycle
time
Cycle
time
S
: Source word
N
: Bit number
TST(350)
S
N
S
: Source word
N
: Bit number
TSTN(351)
S
N
Variations
Executed Each Cycle
TST(350)
Immediate Refreshing Specification
Not supported
Variations
Executed Each Cycle
TSTN(351)
Immediate Refreshing Specification
Not supported