191
Sequence Control Instructions
Section 3-5
3-5-4
JUMP and JUMP END: JMP(004) and JME(005)
Purpose
When the execution condition for JMP(004) is OFF, program execution jumps
directly to the first JME(005) in the program with the same jump number.
JMP(004) and JME(005) are used in pairs.
Ladder Symbols
Variations
Applicable Program Areas
CIO 000000
ON
CIO 000000
OFF
Normal
execution
Reset
Outputs
interlocked
Retained
Retained
OFF
OFF
N: Jump number
JMP(004)
N
N: Jump number
JME(005)
N
Variations
Jumps when OFF/Doesn’t jump when ON
JMP(004)
Immediate Refreshing Specification
Not supported
Variations
Executed Each Cycle for ON Condition
JME(005)
Immediate Refreshing Specification
Not supported
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
Not allowed
OK
OK
Summary of Contents for CJ1G-CPUxx