164
Sequence Input Instructions
Section 3-3
Applicable Program Areas
Operands
N: Bit number
The bit number must be between 0000 and 000F hexadecimal or between
&0000 and &0015 decimal. Only the rightmost bit (0 to F hexadecimal) of the
contents of the word is valid when a word address is specified.
Operand Specifications
Description
LD TST(350), AND TST(350), and OR TST(350) can be used in the program
like LD, AND, and OR; the execution condition is ON when the specified bit in
the specified word is ON and OFF when the bit is OFF. Unlike LD, AND, and
OR, bits in the DM and EM areas can be used as operands in TST(350).
LD TSTN(351), AND TSTN(351), and OR TSTN(351) can be used in the pro-
gram like LD NOT, AND NOT, and OR NOT; the execution condition is OFF
when the specified bit in the specified word is ON and ON when the bit is OFF.
Unlike LD NOT, AND NOT, and OR NOT, bits in the DM and EM areas can be
used as operands in TSTN(351).
Flags
Block program areas
Step program areas
Subroutines
Interrupt tasks
OK
OK
OK
OK
Area
S
N
CIO Area
CIO 0000 to CIO 6143
Work Area
W000 to W511
Holding Bit Area
H000 to H511
Auxiliary Bit Area
A000 to A959
Timer Area
T0000 to T4095
Counter Area
C0000 to C4095
DM Area
D00000 to D32767
EM Area without bank
E00000 to E32767
EM Area with bank
En_00000 to En_32767
(n = 0 to C)
Indirect DM/EM addresses
in binary
@ D00000 to @ D32767
@ E00000 to @ E32767
@ En_00000 to @ En_32767
(n = 0 to C)
Indirect DM/EM addresses
in BCD
*D00000 to *D32767
*E00000 to *E32767
*En_00000 to *En_32767
(n = 0 to C)
Constants
---
#0000 to #000F (binary) or
&0 to &15
Data Registers
DR0 to DR15
Index Registers
---
Indirect addressing using
Index Registers
,IR0 to ,IR15
–2048 to +2047 , IR0 to –2048 to +2047 ,IR15
DR0 to DR15, IR0 to IR15
,IR0+(++) to ,IR15+(++)
,–(– –)IR0 to, –(– –)IR15
Name
Label
Operation
Error Flag
ER
OFF or unchanged (See note.)
Summary of Contents for CJ1G-CPUxx
Page 3: ...iv N o t i c e ...
Page 5: ...vi ...
Page 21: ...xxii Conformance to EC Directives 6 ...
Page 35: ......
Page 1131: ...1110 CJ series Instruction Execution Times and Number of Steps Section 4 2 ...