7. PARAMETERS
7 - 48
No./
symbol/name
Setting
digit
Function
Initial
value
[unit]
Control mode
CP/BCD
CL
PS
PC27
*COP6
Function
selection C-6
_ _ _ x [AL. 10 Undervoltage] detection method selection
Set this parameter when [AL. 10 Undervoltage] occurs due to distorted power supply
voltage waveform while using FR-RC-(H) or FR-CV-(H).
0: [AL. 10] not occurrence
1: [AL. 10] occurrence
This digit is not available with MR-J4-03A6-RJ servo amplifiers.
0h
_ _ x _ Main circuit power supply selection
Select a voltage to be connected to the main circuit power supply with an
MR-J4-03A6-RJ servo amplifier.
0: 48 V DC
1: 24 V DC
When using 24 V DC for the main circuit power supply, set "1" to this digit.
This digit is not available with MR-J4-_A_-RJ 100 W or more servo amplifiers.
The characteristics of the servo motor vary depending on whether 48 V DC or 24 V DC
is used. For details, refer to "Servo Motor Instruction Manual (Vol. 3)".
0h
_ x _ _ Undervoltage alarm selection
Select the alarm and warning that occurs when the bus voltage drops to the
undervoltage alarm level.
0: [AL. 10] regardless of servo motor speed
1: [AL. E9] at servo motor speed 50 r/min (50 mm/s) or less, [AL. 10] at over 50 r/min
(50 mm/s)
0h
x _ _ _ For manufacturer setting
0h
PC28
*COP7
Function
selection C-7
_ _ _ x For manufacturer setting
0h
_ _ x _
0h
_ x _ _
0h
x _ _ _ Linear scale multipoint Z-phase input function selection
When two or more reference marks exist during the full stroke of the linear encoder,
set "1".
0: Disabled
1: Enabled
This parameter setting is used by servo amplifiers with software version A5 or later.
This digit is not available with MR-J4-03A6-RJ servo amplifiers.
0h
PC30
STA2
Home
position
return
acceleration
time constant
This parameter is used when a home position return is executed with the program
method. Set the acceleration time constant at the home position return. Set an
acceleration time from 0 r/min or 0 mm/s to the rated speed.
Additionally, when 20000 ms or more value is set, it will be clamped to 20000 ms.
Setting range: 0 to 50000
0
[ms]
PC30
STA2
Acceleration
time constant
2
Set an second acceleration time constant for the automatic operation of the indexer
method.
Set an acceleration time from 0 r/min to the rated speed.
Additionally, when 20000 ms or more value is set, it will be clamped to 20000 ms.
Setting range: 0 to 50000
0
[ms]
PC31
STB2
Home
position
return
deceleration
time constant
This parameter is used when a home position return is executed with the program
method. Set the deceleration time constant at the home position return. Set a
deceleration time from the rated speed to 0 r/min or 0 mm/s.
Additionally, when 20000 ms or more value is set, it will be clamped to 20000 ms.
Setting range: 0 to 50000
0
[ms]
www.kavrammuhendislik.com.tr
Summary of Contents for MELSERVO MR-J4-03A6-RJ
Page 27: ...1 FUNCTIONS AND CONFIGURATION 1 12 MEMO www kavrammuhendislik com tr ...
Page 127: ...3 DISPLAY AND OPERATION SECTIONS 3 54 MEMO www kavrammuhendislik com tr ...
Page 275: ...5 HOW TO USE THE PROGRAM 5 68 MEMO www kavrammuhendislik com tr ...
Page 305: ...6 HOW TO USE INDEXER 6 30 MEMO www kavrammuhendislik com tr ...
Page 405: ...7 PARAMETERS 7 100 MEMO www kavrammuhendislik com tr ...
Page 419: ...8 TROUBLESHOOTING 8 14 MEMO www kavrammuhendislik com tr ...
Page 423: ...9 OPTIONS AND PERIPHERAL EQUIPMENT 9 4 MEMO www kavrammuhendislik com tr ...
Page 607: ...MEMO www kavrammuhendislik com tr ...