MPH-02, MPB-02, MPD-02
Handling, Diagnostic and Service Functions
10-19
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Note:
The control section is configured at the factory and the
configuration is displayed in parameter P-0-1520 for diagnostic
purposes (type designation in plain text)!
•
S-0-0140, Controller type
•
P-0-1506, Circuit board code optional module 1
•
P-0-1507, Circuit board code optional module 2
•
P-0-1508, Circuit board code optional module 3
•
P-0-1509, Circuit board code master communication
•
P-0-1510, Circuit board code power section
•
P-0-1511, Circuit board code control section
•
P-0-1520, Control section type
During the initialization phase the drive, apart from checking the existing
configuration, carries out some additional checks. Errors detected during
the checks are classified according to their cause.
General malfunction of a circuit board with specific error messages:
•
F8091 Power section defective
•
F8122 Control section defective
Configuration of control section not allowed, i.e. an optional card was
plugged into a slot that does not support this card (observe allowed
combinations of the individual optional modules; see documentation
"Project Planning Manual for Control Section"):
•
F8118 Invalid power section/firmware combination
•
F8120 Invalid control section/firmware combination
Hours-Run Meter
Brief Description
There are hours-run meters available in the drive that separately record
the operating time for control section and power section. The respective
operating time is displayed in the parameters P-0-0190 or P-0-0191.
These times are directly stored from the control section or power section
so that assignment is maintained also for servicing.
•
P-0-0190, Operating hours control section
•
P-0-0191, Operating hours power section
The parameter
P-0-0190, Operating hours control section
displays the
operating time of the drive’s control section. The unit is seconds.
The time the drive has been switched on is considered to be the operating
time of the control section.
The parameter
P-0-0191, Operating hours power section
displays the
operating time of the drive’s power section when drive enable has been
set. The unit is seconds.
The time during which the output stage has been enabled is considered to
be the operating time of the power section.