7-94
Operating Modes
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Possible counter measures:
•
increasing the filter time constant
•
reducing the changes in the additive position command value
•
increasing the limit values for velocity and acceleration
In the "register controller" synchronization mode all further changes of the
additive position command value are smoothed by a 1
st
order filter. The
time constant of the filter is set in parameter
P-0-0060, Filter time
constant additional pos. command
.
Note:
The status bit "synchronization completed" is set when the
absolute synchronization has been reached and won’t be
cleared even with further changes in
S-0-0048, Position
command value additional
.
DK000046v01_en.fh7
t
t
0
0
velocity
of salve axis
operating mode
activated
1
t
0
1
0
P-0-0142
step 1
step 2
P-0-0143
change of additive position
command value (S-0-0048)
P-0-0142
synchronization
reaction
to change of
additive pos. cmd value
P-0-0060
synchronization
completed
(P-0-0152, bit 0)
Fig. 7-73:
"Register controller" synchronization mode
During synchronization in the "register controller" mode the command
values are monitored with regard to
S-0-0091, Bipolar velocity limit
value
and
S-0-0138, Bipolar acceleration limit value
. If the command
values exceed the limit values, the error messages
F2037 Excessive
position command difference
or
F2039 Maximum acceleration
exceeded
are generated.
Possible counter measures:
•
increasing the filter time constant
•
reducing the changes in the additive position command value
•
increasing the limit values for velocity and acceleration
"Register Controller" Mode
(P-0-0155, bit 0 = 1)