MPH-02, MPB-02, MPD-02
Handling, Diagnostic and Service Functions
10-47
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Note:
The message "Load new Param.?" does not always appear
when the MMC hasn’t been plugged (depending on the
previous configuration of the replacement device)!
Replacing a Device without Stationarily Plugged MMC
An MMC temporarily plugged in the controller can be used as update
medium for firmware and as update and backup medium for parameter
values.
Before dismounting defective device save drive parameter values, if
possible. To do this, switch drive off and on again, then save parameter
values in communication phase "P2".
Parameter values of defective device can be saved via:
•
Control panel of the controller with temporarily plugged MMC
("hot plug")
By pressing the buttons on the control panel in a certain order
C2600
Copy data from flash to MMC command
(P-0-4092) can be started.
By doing this the active parameter values [according to
S-0-0192, IDN-
list of backup operation data
and
P-0-0195, IDN list of retain data
(replacement of devices)
] are copied from the controller-internal
memory to an MMC temporarily plugged in the controller.
Note:
If the MMC does not remain stationarily (permanently) plugged
in the device, it may be temporarily plugged
in the switched-
on device after the booting phase
and removed again ("hot
plug" or "hot unplug").
See also "Control Panel of the IndraDrive Controllers" in chapter
"Handling, Diagnostic and Service Functions"
•
"DriveTop" commissioning tool
By selecting the respective menu item, the parameter values
according to the list parameters S-0-0192 and P-0-0195 are stored on
an external data carrier (hard disk, floppy disk or the like) [serial
communication with the controller or via SYSDA/SERCOS interface].
•
Control master
The parameter values according to the list parameters S-0-0192 and
P-0-0195 are stored on a master-side data carrier by the control
master.
De-energize drive; wait for DC bus to discharge!
DANGER
Live conductor bars (higher than 50 V), even if mains
voltage switched off!
Electric shock when touching!
⇒
Wait for the DC bus (L+/L-) to discharge; before
touching the conductor bar check whether below
50 V!
Notes on how to mount and dismount the controller see
documentation "Project Planning Manual for Power Sections"!