MPH-02, MPB-02, MPD-02
Handling, Diagnostic and Service Functions
10-9
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
After loading the basic parameters the controller signals "RL" if a Rexroth
motor with motor encoder data memory was connected. By means of
•
pressing the "Esc" button at the control panel
- or -
•
command
S-0-0099, C0500 Reset class 1 diagnostics
the motor-specific control loop parameter values saved in the motor
encoder are loaded for adjusting the controller to the motor.
If the original status of the motor-specific control loop parameter values is
to be reestablished during commissioning, this is done, in the case of
motors with encoder data memory, by starting
•
S-0-0262, C07_x Load defaults procedure command
.
CAUTION
⇒
By executing this command control loop parameter
values that have already been optimized are possibly
overwritten!
Note:
By automatic reset the
P-0-4090, Index for C07 Load
defaults procedure
parameter is correctly preset!
Note:
In the case of motors without encoder data memory, loading
the motor-specific control loop parameter values by means of
the "load defaults procedure" command is impossible! The
values can be loaded from a data base of the "DriveTop"
commissioning tool.
Respective diagnostic command message:
•
C07_0 Load defaults procedure com. (load controller param.)
Respective diagnostic messages in the case of possible command errors:
•
C0702 Default parameters not available
•
C0703 Default parameters invalid
•
C0704 Parameters not copyable
•
C0706 Error when reading the controller parameters
See also "Initial Commissioning/Serial Commissioning" in chapter
"Commissioning"
When "volatile storage" was set in
S-0-0269, Parameter buffer mode
the
parameter values are not automatically stored in the drive-internal flash
memory. The application-specific parameter values therefore, after
complete input by means of
•
S-0-0264, C2200 Backup working memory procedure command
have to be saved drive-internally in the flash memory. This guarantees
that the parameter values suitable for the axis are automatically loaded to
the controller’s working memory from the flash memory after the drive is
switched on again.
Respective diagnostic command message:
•
C2200 Backup working memory procedure command
Loading Motor-Specific Control
Loop Parameter Values
With Parameter Buffer Mode
"Volatile Storage"