MPH-02, MPB-02, MPD-02
Drive Control
6-73
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
The drive provides two possibilities of determining and monitoring a
limitation of the working range (travel range):
•
monitoring
position limit values
(software limit switch)
Monitoring the motor position for exceeding one of the two position
limit values (positive/negative
→
S-0-0049/S-0-0050) by the homed
actual position value (S-0-0403), i.e. value related to the machine zero
point.
•
monitoring
travel range limit switches
Monitoring for activation of one of the two travel range limit switches
(Limit+, Limit-) that are connected to the digital inputs of the drive.
Note:
The functionality of the travel range limit switches is only
guaranteed if the respective digital inputs have been
configured for this purpose!
See "Digital Inputs/Outputs" in chapter "Extended Drive
Functions"
•
2 travel range limit switches (Limit+, Limit-) monitored at the drive
•
signal behavior of travel range limit switches (N/C and N/O) can be set
•
travel range limit switches activated via parameter
•
reaction (error/warning) when exceeding travel range can be set
•
status display of travel range limit switches
•
command values monitored for validity when limit switch activated
•
travel range limit switches evaluated and position limit value monitor
activated in 2 ms clock
•
2
position limit values ("software limit switch") that can be
parameterized; only operational when axis has been homed
•
reaction (error/warning) when exceeding position limit values can be
set
•
position limit values activated via parameter
•
automatic reference to measuring system that has been homed
•
command values monitored for validity when position limit values
exceeded
•
S-0-0012, Class 2 diagnostics
•
S-0-0049, Positive position limit value
•
S-0-0050, Negative position limit value
•
S-0-0055, Position polarities
•
S-0-0147, Homing parameter
•
S-0-0403, Position feedback value status
•
P-0-0090, Travel range limit parameter
•
P-0-0222, Travel range limit switch inputs
•
E2053 Target position out of travel range
•
E8029 Positive position limit exceeded
•
E8030 Negative position limit exceeded
•
E8042 Both travel range limit switches activated
•
E8043 Positive travel range limit switch activated
•
E8044 Negative travel range limit switch activated
Realizing Travel Range
Monitoring
Features of Travel Range Limit
Switch
Features of Position Limit
Values
Pertinent Parameters
Pertinent Diagnostic Messages