5-4
Motor, Mechanical Axis System, Measuring Systems
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Note:
In the case of MHD, MKD, LSF, MBS and MKE motors, the
motor temperature, due to the sensor characteristics, can only
be determined very inexactly. Shutdown is caused by abrupt
resistance increase of the sensor at maximum temperature!
The warning and shutdown thresholds (S-0-0201 and
S-0-0204) to be set cannot be used!
Third-party motors may include temperature sensors that do not
correspond to the standard type sensors. This information is given to the
controller via the
P-0-0512, Temperature sensor
parameter. The
respective resistance temperature characteristic then has to be input
manually as a table of values in the
P-0-0513, Temperature sensor
characteristic
parameter.
Third-party motors without installed temperature sensor can also be
operated with IndraDrive controllers, but in the case of overload they are
not
protected on the controller side against thermal damage! The
temperature monitor has to be switched off in the mentioned case,
because otherwise the controller demands a temperature sensor to be
connected.
See also "Third-Party Motors at IndraDrive Controllers" in the same
chapter
Notes on Commissioning
For the following parameters it is necessary to replace the default value
by an adjusted value during commissioning.
Rexroth motors with the characteristic temperature sensor number "1"
(MHD, MKD, LSF, MBS motors) or "4" (MKE motors):
→
No temperature sensor relevant parameter setting required!
Rexroth motors with the characteristic temperature sensor number "2",
"3" or "5" (2AD, ADF, 1MB, MAD, MAF or SF motors):
•
S-0-0201, Motor warning temperature
Third-party motors with the characteristic temperature sensor number "2",
"3" or "5":
•
P-0-0512, Temperature sensor
•
S-0-0201, Motor warning temperature
•
S-0-0204, Motor shutdown temperature
Third-party motors with the characteristic temperature sensor number
"100":
•
P-0-0512, Temperature sensor
•
P-0-0513, Temperature sensor characteristic
•
S-0-0201, Motor warning temperature
•
S-0-0204, Motor shutdown temperature
Note:
The value in parameter S-0-0201 has to be smaller than the
value of S-0-0204!
It is not necessary to separately activate the temperature monitor of the
motor. You only have to enter the appropriate values in the respective
parameters.
Third-Party Motors
Relevant Parameters
Activating the Function