10-78
Handling, Diagnostic and Service Functions
MPH-02, MPB-02, MPD-02
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Communication via RS485 Interface
The communication via the RS485 interface allows realizing a serial bus
with the following data:
•
it is possible to connect up to 31 drives with one bus master
•
transmission rates from 9600 to 115,200 Baud
•
max. transmission distance 500 m
•
semi-duplex operation via 2-wire line
•
ASCII protocol or SIS protocol (8-bit each)
•
parity bit according to parameter
P-0-4095, RS-232/485 Parity
•
one stop bit
Note:
Communication via RS485 is only possible in conjunction with
an external RS232/485 converter.
Operating Several Drives with DriveTop
•
commissioning several drive controllers without plugging the interface
cable into a different connection (central parameterization and
diagnosis connection)
•
realizing a central PC-based visualization unit
PC with DriveTop
PLC
drive
controller
n
drive
controller
n+1
drive
controller
n+2
drive
controller
n+3
RS232
RS485 bus
master communication
(e.g. parallel I/O or field
bus)
RS232/RS485
converter
RS232/
RS485
converter
RS232/
RS485
converter
RS232/
RS485
converter
RS232/
RS485
converter
DF0021v1.fh7
Fig. 10-37: Operating Several Drives with DriveTop