RS-485 Communication Features
251
Comm. Address
Parameter
Scale
Unit
Assigned Content by Bit
command
B0
0: Stop command, 1: Run command
Example: Forward operation command 0003h,
Reverse operation command 0001h
0h0383
Acceleration
time
0.1
s
Acceleration time setting
0h0384
Deceleration
time
0.1
s
Deceleration time setting
0h0385
Virtual digital
input control
(0: Off, 1:On)
-
-
BI5
Reserved
-
Reserved
B8
Reserved
B7
Virtual DI 8(CM.77)
B6
Virtual DI 7(CM.76)
B5
Virtual DI 6(CM.75)
B4
Virtual DI 5(CM.74)
B3
Virtual DI 4(CM.73)
B2
Virtual DI 3(CM.72)
B1
Virtual DI 2(CM.71)
B0
Virtual DI 1(CM.70)
0h0386
Digital output
control
(0:Off, 1:On)
-
-
BI5
Reserved
BI4
Reserved
BI3
Reserved
BI2
Reserved
BI1
Reserved
BI0
Reserved
B9
Reserved
B8
Reserved
B7
Reserved
B6
Reserved
B5
Reserved
B4
Relay 4 (I/O board, OU.31: None)
B3
Relay 3 (I/O board, OU.31: None)
B2
Relay 2 (I/O board, OU.31: None)
B1
Q1 (I/O board, OU.33: None)
B0
Relay 1 (I/O board, OU.31: None)
0h0387
Reserved
-
-
Reserved
0h0388
PID reference 0.1
%
PID reference command
0h0389
PID feedback
value
0.1
%
PID feedback value
0h038A
Motor rated
current
0.1
A
-
0h038B
Motor rated
voltage
1
V
-
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......