343
Type
Cause
Remedy
a complete stop when the
inverter output stops.
sufficiently, because DC braking is
not operating normally.
Increase the set value for the DC
braking current.
Increase the set value for the DC
braking stopping time.
The output frequency does
not increase to the frequency
reference.
The frequency reference is within
the jump frequency range.
Set the frequency reference
higher than the jump frequency
range.
The frequency reference is
exceeding the upper limit of the
frequency command.
Set the upper limit of the
frequency command higher than
the frequency reference.
Because the load is too heavy, the
stall prevention function is working.
Replace the inverter with a model
with increased capacity.
The cooling fan does not
rotate.
The control parameter for the
cooling fan is set incorrectly.
Check the control parameter
setting for the cooling fan.