225
Learning Protection Features
Fan Fault Detection
Group
Code
Name
LCD Display
Parameter Setting Setting range Unit
Pr
79
Cooling fan fault
selection
FAN Trip
Mode
0
Trip
OU
31
Multi-function
relay 1
Relay 1
8 FAN Warning
-
OU
33
Multi-function
output 1
Q1 Define
Fan Fault Detection Setting Details
Code
Description
Pr.79 FAN
Trip Mode
Set the cooling fan fault mode.
Setting
Function
0
Trip
The inverter output is shut off and the fan trip is
displayed when a cooling fan error is detected.
1
Warning
When OU.33 (Q1 Define) and OU.31 (Relay1) are
set to 8 (FAN Warning), the fan warning signal is
output, but operation continues.
Caution:
when
the inverter inside temperature rises above a
certain level, output is shut off due to activation of
inverter overheat protection.
Lifetime diagnosis for fans
Fan operating hours is monitored and can be viewed at Pr.86, FAN Time Perc. The (%) is based on
50,000 hours of operation. A Fan warning will be displayed on the keypad when fan usage has
reached the percentage entered in Pr-87, (Fan exchange level). When exchanging fans, you can
initialize the accumulated value to 0 by setting Pr.88, FAN Time Rst to 1.
Group Code Name
LCD Display
Setting value
Setting Range Unit
Pr
86
Accumulated percent
of fan usage
FAN Time Perc
0.0
0.0-6553.5
%
87
Fan exchange warning
Level
FAN Exchange
level
90.0
0.0-100.0
%
Pr
88
Initialize operation time
of cooling fans
FAN Time Rst
0
No
-
-
1
Yes
OU
31
Multi-function relay 1
Relay 1
38
FAN
Exchange
-
33
Multi-function output 1 Q1 Define
*Available on LCD keypad only.
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......