Learning Advanced Features
205
Fault Trip Output using Multi-Function Output Terminal and Relay
The inverter can output a fault state using multi-function output terminal (Q1) and relay (Relay 1).
Group
Code
Name
LCD
Display
Parameter Setting
Setting
Range
Unit
OU
30
Fault trip
output
mode
Trip Out
Mode
010
-
bit
31
Multi-
function
relay1
Relay 1
29
Trip
-
-
33
Multi-
function
output1
Q1 Define 14
Run
-
-
53
Fault trip
output on
delay
TripOut
OnDly
0.00
0.00–
100.00
sec
54
Fault trip
output off
delay
TripOut
OffDly
0.00
0.00–
100.00
sec
Fault Trip Output by Multi-function Output Terminal and Relay - Setting Details
Code
Description
OU.30 Trip Out
Mode
Fault relay operates based on the fault output settings.
Item
bit on
bit off
Keypad
LCD keypad
Select 29(Trip Mode) at codes OU. 31 for Relay1 terminal or OU.33 for the Q1
terminal . When a fault occurs the relevant relay or terminal will operate.
Depending on the fault type, the relay or terminal operation can be configured as
shown in the table below.
Setting
Function
bit3
bit2
bit1
Operates when low voltage fault occur
Operates when faults other than low voltage
occur
Operates when auto restart fails (Pr. 08
–
09)
OU.31 Relay1
Set relay output (Relay 1) to 29 (Trip Mode) for fault output.
OU.33 Q1 Define
Set multi-function output terminal (Q1) to 29 (Trip Mode) for fault output. Q1 is
open collector transistor output.
OU.53 TripOut
If a fault occurs, relay or multi-function output operates after the time delay set in
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......