Table of Functions
268
Expanded Function group (PAR
→
→
→
→
Ad)
In the following table, the data shaded in grey will be displayed when a related code has been
selected.
SL
: Sensorless vector control (dr.09) , I – IM Sensorless, P – PM Sensorless
*
O/X
: Write-enabled during operation,
7/L/A
: Keypad/LCD keypad/Common
Code
Comm.
Address
Name
LCD Display
Setting Range
Initial
Value
Property* V/F SL Ref.
00
-
Jump Code
Jump Code
1-99
24
O/A
O
I/P
p.43
01
0h1301
Acceleration
pattern
Acc Pattern
0
Linear
0:
Linear
X/A
O
I/P
p.88
02
0h1302
Deceleration
pattern
Dec Pattern
1
S-curve
X/A
O
I/P
p.88
03
14
0h1303
S-curve
acceleration
start point
gradient
Acc S Start
1-100(%)
40
X/A
O
I/P
p.88
04
14
0h1304
S-curve
acceleration end
point gradient
Acc S End
1-100(%)
40
X/A
O
I/P
p.88
05
15
0h1305
S-curve
deceleration
start point
gradient
Dec S Start
1-100(%)
40
X/A
O
I/P
p.88
06
15
0h1306
S-curve
deceleration
end point
gradient
Dec S End
1-100(%)
40
X/A
O
I/P
p.88
07
0h1307 Start Mode
Start Mode
0
Acc
0:Acc
X/A
O
I/P
p.96
1
DC-Start
08
16
0h1308 Stop Mode
Stop Mode
0
Dec
0:Dec
X/A
O
I/P
p.97
1
DC-Brake
2
Free-Run
4
Power
Braking
09
0h1309
Selection of
prohibited
rotation
direction
Run Prevent
0
None
0: None X/A
O
I/P
p.81
1
Forward
Prev
2
Reverse Prev
10
0h130A Starting with
Power-on
0
No
0:No
O/A
O
I/P
p.81
14
Displayed when Ad. 01 is set to 1 (S-curve).
15
Displayed when Ad. 02 is set to 1 (S-curve).
16
DC braking and power braking (Ad.08, stop mode options 1 and 4) are not available when dr.09
(Control Mode) is set to 6 (PM Sensorless).
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......