Learning Advanced Features
95
Group
Code
Name
LCD
Display
Parameter Setting
Setting
Range
Unit
mode
bA
20
auto
tuning
Auto
Tuning
3
Rs+Lsigm
a
0–6
-
Auto Torque Boost-2
In V/F operation, this adjusts the output voltage during starting if motor does not rotate due to a
low output voltage and due to a lack of starting torque.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range Unit
Dr
15
torque boost
mode
Torque Boost 2
Auto2
0–2
-
Output Voltage Setting
Output voltage adjustment is required when a motor’s rated voltage differs from the input voltage
to the inverter. Set bA.15 to configure the motor’s rated operating voltage. The set voltage
becomes the output voltage at the inverter’s base frequency. When the motor’s voltage rating is
lower than the input voltage at the inverter, the inverter adjusts the voltage and supplies the motor
with the voltage set at bA.15 (motor rated voltage). When the inverter operates above the base
frequency or if the motor’s rated voltage is higher than the input voltage at the inverter, the
maximum output voltage will be equal to the input voltage.
If bA.15 (motor rated voltage) is set to 0, the inverter corrects the output voltage based on the input
voltage in the stopped condition. When the input voltage is lower than the parameter setting, the
input voltage will be the inverter output voltage.
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
bA
15
Motor rated voltage
Motor Volt
230 or 460 model
dependant
0, 170
–
480
V
480V
170V
Output voltage
Base freq.
Output freq.
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......