Installing the Inverter
22
Step 3 Power Terminal Wiring
The following illustration shows the terminal layout on the power terminal block. Refer to the
detailed descriptions to understand the function and location of each terminal before making
wiring connections. Ensure that the cables selected meet or exceed the specifications in 1.5
Cable
Selection
before installing them.
•
Apply rated torques to the terminal screws. Loose screws may cause short circuits and
malfunctions. Tightening the screw too much may damage the terminals and cause short circuits
and malfuctions.
•
Use copper wires only with 600V, 75
℃
rating for the power terminal wiring, and 300V, 75
℃
rating
for the control terminal wiring.
•
Do not connect two wires to one terminal when wiring the power.
•
Power supply wiring must be connected to the R, S, and T terminals. Connecting them to the output
(U, V, W terminals) will cause damage to the inverter. Arrangement of the input phase sequence is
not critical.
•
Motor must be connected to the U, V, and W Terminals.