RS-485 Communication Features
253
Inverter Memory Control Area Parameter (Read and Write)
Comm.
Address
Parameter
Scale
Unit
Changeable
During Operation
Function
0h03E0
Save parameters -
-
X
0: No, 1:Yes
0h03E1
Monitor mode
initialization
-
-
O
0: No, 1:Yes
0h03E2
Parameter
initialization
-
-
X
0: No, 1: All Grp, 2: Drv Grp
3: bA Grp, 4: Ad Grp, 5: Cn
Grp
6: In Grp, 7: OU Grp, 8: CM
Grp
9: AP Grp, 12: Pr Grp, 13: M2
Grp
Setting is prohibited during
fault interruptions.
0h03E3
Display changed
parameters
-
-
O
0: No, 1: Yes
0h03E4
Reserved
-
-
-
-
0h03E5
Delete all fault
history
-
-
O
0: No, 1: Yes
0h03E6
Delete user-
registrated codes
-
-
O
0: No, 1: Yes
0h03E7
Hide parameter
mode
0
Hex
O
Write: 0-9999
Read: 0: Unlock, 1: Lock
0h03E8
Lock parameter
mode
0
Hex
O
Write: 0-9999
Read: 0: Unlock, 1: Lock
0h03E9
Easy start on
(easy parameter
setup mode)
-
-
O
0: No, 1: Yes
0h03EA
Initializing power
consumption
-
-
O
0: No, 1: Yes
0h03EB
Initialize inverter
operation
accumulative
time
-
-
O
0: No, 1: Yes
0h03EC
Initialize cooling
fan accumulated
operation time
-
-
O
0: No, 1: Yes
Note
•
When setting parameters in the inverter memory control area, the values are reflected to the
inverter operation and saved. Parameters set in other areas via communication are reflected
to the inverter operation, but are not saved. All set values are cleared following an inverter
power cycle and revert back to its previous values. When setting parameters via
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......