Learning Advanced Features
87
Acc/Dec Time Setup via Multi-function Terminals – Setting Details
Code
Description
bA. 70–82 Acc Time 1–7 Set multi-step acceleration time1
–
7.
bA.71–83 Dec Time 1–7 Set multi-step deceleration time1
–
7.
In.65–69
Px Define (P1–P5)
Choose and configure the terminals to use for multi-step Acc/Dec time
inputs.
Configuration
Description
11
XCEL-L
Acc/Dec command-L
12
XCEL-M
Acc/Dec command-M
49
XCEL-H
Acc/Dec command-H
Acc/Dec commands are recognized as binary code inputs and will control
the acceleration and deceleration based on parameter values set with
bA.70
–
bA.83.
If, for example, the P4 and P5 terminals are set as XCEL-L and XCEL
respectively, the following operation will be available.
Acc/Dec time
P5
P4
0
-
-
1
-
2
-
3
In.89 In Check Time
Set the time for the inverter to check for other terminal block inputs. If
In.89 is set to 100ms and a signal is supplied to the P4 terminal, the inverter
searches for other inputs over the next 100ms. When the time expires, the
Acc/Dec time will be set based on the input received at P4.
P4
P5
Frequency
Acc0
Acc1
Acc2
Acc3
Dec0
Dec1
Dec2
Dec3
Run cmd
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......