RS-485 Communication Features
237
retains all the existing values even after the power has been turned off.
Setting address 0h03E0 to 0 and then setting it again to 1 via communication allows the existing
parameter settings to be saved. However, setting address 0h03E0 to 1 and then setting it to 0 does
not carry out the same function. Parameters defined by communication can only be saved using an
LCD keypad.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
range
Unit
CNF*
48
Save parameters
Parameter
Save
0
No
0 -1
-
1
Yes
*Available on an LCD keypad only.
Total Memory Map for Communication
Communication Area
Memory Map
Details
Communication common compatible
area
0h0000-
0h00FF
Benshaw S Series, SG, GX compatible
area
Parameter registration type area
0h0100-
0h01FF
Areas registered at CM.31–38 and
CM.51–58
0h0200-
0h023F
Area registered for User Group
0h0240-
0h027F
Area registered for Macro Group
0h0280-
0h02FF
Reserved
Communication common area
0h0300-0h037F Inverter monitoring area
0h0380-
0h03DF
Inverter control area
0h03E0-
0h03FF
Inverter memory control area
0h0400-
0h0FFF
Reserved
0h1100
dr Group
0h1200
bA Group
0h1300
Ad Group
0h1400
Cn Group
0h1500
In Group
0h1600
OU Group
0h1700
CM Group
0h1800
AP Group
0h1B00
Pr Group
0h1C00
M2 Group
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......