RS-485 Communication Features
234
Code
Description
CM.04 Int485 Mode
Set a communication configuration. Set the data length, parity check
method, and the number of stop bits.
Setting
Function
0
D8/PN/S1
8-bit data / no parity check / 1 stop bit
1
D8/PN/S2
8-bit data / no parity check / 2 stop bits
2
D8/PE/S1
8-bit data / even parity / 1 stop bit
3
D8/PO/S1
8-bit data / odd parity / 1 stop bit
CM.05 Resp Delay
Set the response time for the slave (inverter) to react to the request from
the master. Response time is used in a system where the slave device
response is too fast for the master device to process. Set this code to an
appropriate value for smooth master-slave communication.
Setting Operation Command and Frequency
To select the built-in RS485 communication as the source of command, set the Frq code to 6
(Int485) on the keypad (basic keypad with 7-segment display). On an LCD keypad, set the DRV code
to 3 (Int485). Then, set common area parameters for the operation (start/Stop) command and
frequency (speed) via communication.
Group
Code
Name
LCD Display
Parameter Setting
Setting range
Unit
Pr
12
Speed
command
loss
operation
mode
Lost Cmd
Mode
1
Free-Run
0-5
-
13
Time to
determine
speed
command
Lost Cmd
Time
1.0
0.1-120
s
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......