Learning Advanced Features
69
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
In
01
Frequency at
maximum analog
input
Freq at
100%
60.00
0
–
Maximum
Frequency
Hz
50
I2 input monitor
I2 Monitor 0.00
0.00
–
24.00 mA
52
I2 input filter time
constant
I2 Filter
10
0
–
10000
ms
53
I2 minimum input
current
I2 Curr x1
4.00
0.00
–
20.00 mA
54
I2 output at
minimum current
(%)
I2 Perc y1
0.00
0
–
100
%
55
I2 maximum
input current
I2 Curr x2
20.00
0.00
–
24.00 mA
56
I2 output at
maximum
current (%)
I2 Perc y2
100.00
0.00
–
100.00
%
61
I2 rotation
direction options
I2 Inverting 0
No
0
–
1
-
62
I2 Quantizing
level
I2
Quantizing
0.04
0*, 0.04–
10.00
%
* Quantizing is disabled if ‘0’ is selected.
Input Current (I2) Setting Details
Code
Description
In.01 Freq at 100%
Configures the frequency reference for operation at the maximum current
(when In.56 is set to 100%).
•
If In.01 is set to 60.00Hz, and default settings are used for In.53–56, 20mA
input current (max) to I2 will produce a frequency reference of 60.00Hz.
•
If In.56 is set to 50.00 (%), and default settings are used for In.01 (60Hz)
and In.53–55, 20mA input current (max) to I2 will produce a frequency
reference of 30.00Hz (50% of 60Hz).
In.50 I2 Monitor
Used to monitor input current at I2.
In.52 I2 Filter
Configures the time for the operation frequency to reach 63% of target
frequency based on the input current at I2.
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......