Maintenance
348
Inspection
area
Inspection item Inspection details
Inspection method Judgment
standard
Inspection
equipment
and tighten all
screws.
Display
Display device Is the display
value normal?
Check the
command value
on the display
device.
Specified and
managed
values must
match.
Voltmeter,
Ammeter, etc.
Bi-annual Inspections
Inspection
area
Inspection item
Inspection
details
Inspection
method
Judgment
standard
Inspection
equipment
Motor
Insulation
resistance
Megger test
(between the
input, output
and earth
terminals).
Disconnect the
cables for
terminals U/V/
W and test the
wiring.
Must be above
5 MΩ
DC 500 V Megger
Do not run an insulation resistance test (Megger) on the control circuit as it may result in damage to the
product.
Storage and Disposal
Storage
If you are not using the product for an extended period, store it in the following way:
•
Store the product in the same environmental conditions as specified for operation (refer to 1.3
Installation Considerations
).
•
When storing the product for a period longer than 3 months, store it between 10
˚
C and 30
˚
C, to
prevent depletion of the electrolytic capacitor.
•
Do not expose the inverter to snow, rain, fog, or dust.
•
Package the inverter in a way that prevents contact with moisture. Keep the moisture level
below 70% in the package by including a desiccant, such as silica gel.
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......