Learning Advanced Features
86
Acc/Dec Time Based on Operation Frequency – Setting Details
Code
Description
bA.08
Ramp T Mode
Set the parameter value to 1 (Delta Freq) to set Acc/Dec times based on Maximum
frequency.
Configuration
Description
0
Max Freq
Set the Acc/Dec time based on Maximum
frequency.
1
Delta Freq
Set the Acc/Dec time based on Operation
frequency.
If Acc/Dec times are set to 5 seconds, and multiple frequency references are used in
the operation in 2 steps, at 10Hz and 30 Hz, each acceleration stage will take 5
seconds (refer to the graph below).
Multi-step Acc/Dec Time Configuration
Acc/Dec times can be configured via digital input terminals by setting the ACC (acceleration time)
and dEC (deceleration time) codes in the Operation group.
Group
Code
Name
LCD Display
Parameter Setting Setting Range Unit
Operation
ACC
Acceleration time
Acc Time
20.0
0.0–600.0
sec
dEC
Deceleration time
Dec Time
30.0
0.0–600.0
sec
bA
70
–
82
Multi-step
acceleration time1
–
7
Acc Time 1
–
7 x.xx
0.0–600.0
sec
71
–
83
Multi-step
deceleration time1
–
7
Dec Time 1
–
7 x.xx
0.0–600.0
sec
In
65
–
69
Px terminal
configuration
Px Define
(Px: P1–P5)
11 XCEL-L
0–54
-
12 XCEL-M
49 XCEL-H
89
Multi-step command
delay time
In Check Time 1
1–5000
ms
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......