RS-485 Communication Features
250
Comm. Address Parameter
Scale
Unit Assigned content by bit
B3
Lost command
B2
Inverter Overload
B1
Underload
B0
Overload
0h0335 -0h033F
Reserved
-
-
-
0h0340
On Time date
0
Day Total number of days the inverter has
been powered on
0h0341
On Time minute
0
Min
Total number of minutes excluding the
total number of On Time days
0h0342
Run Time date
0
Day Total number of days the inverter has
driven the motor
0h0343
Run Time minute
0
Min
Total number of minutes excluding the
total number of Run Time days
0h0344
Fan Time date
0
Day Total number of days the heat sink fan has
been running
0h0345
Fan Time minute
0
Min
Total number of minutes excluding the
total number of Fan Time days
0h0346
-0h0348
Reserved
-
-
-
0h0349
Reserved
-
-
-
0h034A
Option 1
-
-
0: None, 9: CANopen
0h034B
Reserved
-
-
0h034C
Reserved
Control Area Parameter (Read/ Write)
Comm. Address
Parameter
Scale
Unit
Assigned Content by Bit
0h0380
Frequency
command
0.01
Hz
Command frequency setting
0h0381
RPM
command
1
rpm
Command rpm setting
0h0382
Operation
command
-
-
B7
Reserved
B6
Reserved
B5
Reserved
B4
Reserved
B3
0
1: Free-run stop
B2
0
1: Trip initialization
B1
0: Reverse command, 1: Forward
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......