Learning Advanced Features
203
Code
Description
Eq during acceleration:
Operation frequency
≧
Detect frequency
Eq during deceleration:
Operation
frequency>(Detected frequency
–
Detected
frequency width/2)
Ex:
OU.57, FDT Frequency = 30 Hz.
OU.58, FDT Band = 10 Hz.
FDT-4 functions as shown in the graph below.
5
Overload
Outputs a signal when the motor overload is detected
based on Pr.18 and Pr.19.
6
IOL
Outputs a signal when the inverter trips on an inverter
overload fault.
7
Underload
Outputs a signal when the inverter trips on an under
load fault.
8
Fan Warning
Outputs a signal at fan fault warning.
9
Stall
Outputs a signal when a motor is overloaded and
stalled.
10
Over voltage
Outputs a signal when the inverter DC link voltage
rises above the over voltage protection level.
11
Low Voltage
Outputs a signal when the inverter DC link voltage
drops below the low voltage protective level.
12
Over Heat
Outputs signal when the inverter overheats.
13
Lost command
Outputs a signal when there is a loss of the analog
input.
Outputs a signal when RS-485 communication
command is lost.
Outputs a signal when an expansion I/O card is
installed and signal is lost.
14
RUN
Outputs a signal when operation command (run) is
entered and the inverter outputs voltage.
There is no output during DC braking at start.
30Hz
25Hz
Q1
Frequency
Run cmd
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......