Maintenance
346
Inspection
area
Inspection item
Inspection
details
Inspection method Judgment
standard
Inspection equipment
Input/Output
circuit
Smoothing
capacitor
Is there any
leakage
from the
inside?
Visual inspection
No
abnormality
-
Is the
capacitor
swollen?
Cooling
system
Cooling fan
Is there any
abnormal
vibration or
noise?
Turn off the
system and check
operation by
rotating the fan
manually.
Fan rotates
smoothly
-
Display
Measuring
device
Is the
display
value
normal?
Check the display
value on the
panel.
Check and
manage
specified
values.
Voltmeter, ammeter,
etc.
Motor
All
Is there any
abnormal
vibration or
noise?
Visual inspection
No
abnormality
-
Is there any
abnormal
smell?
Check for
overheating or
damage.
Annual Inspections
Inspection
area
Inspection item Inspection details
Inspection method Judgment
standard
Inspection
equipment
Input/Output
circuit
All
Megger test
(between
input/output
terminals and and
earth terminal)
Disconnect
inverter and short
R/S/T/U/V/W
terminals, and
then measure
from each
terminal to the
ground terminal
using a Megger.
Must be
above 5 MΩ
DC 500 V
Megger
Is there anything
loose in the
device?
Tighten up all
screws.
No
abnormality
Is there any
evidence of parts
Visual inspection
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......