279
Table of Functions
Code
Comm.
Address
Name
LCD Display Setting Range
Initial
Value
Property
*
V/F SL Ref.
2
KEB-2
78
41
0h144E
Energy buffering
start level
KEB Start
Lev
110.0-200.0(%)
125.0
X/A
O
I/P
p.154
79
41
0h144F
Energy buffering
stop level
KEB Stop
Lev
Cn78~210.0(%)
130.0
X/A
O
I/P
p.154
80
41
0h1450
Energy buffering
P gain
KEB P Gain 0-20000
1000
O/A O
I/P
p.154
81
41
0h1451
Energy buffering
I gain
KEB I Gain
1~20000
500
O/A O
I/P
p.154
82
41
0h1452
Energy buffering
Slip gain
KEB Slip
Gain
0~2000.0%
30.0
O/A O
I
p.154
83
41
0h1453
Energy buffering
acceleration time
KEB Acc
Time
0.0~600.0(s)
10.0
O/A O
I/P
p.154
85
42
0h1455
Flux estimator
proportional
gain1
Flux P Gain1 100-700
370
O/A X
I
p.150
86
42
0h1456
Flux estimator
proportional
gain2
Flux P Gain2 0-100
0
O/A X
I
p.150
87
42
0h1457
Flux estimator
proportional
gain3
Flux P Gain3 0-500
100
O/A X
I
p.150
88
42
0h1458
Flux estimator
integral gain1
Flux I Gain1 0-200
50
O/A X
I
p.150
89
42
0h1459
Flux estimator
integral gain2
Flux I Gain2 0-200
50
O/A X
I
p.150
90
42
0h145A
Flux estimator
integral gain3
Flux I Gain3 0-200
50
O/A X
I
p.150
91
42
0h145B
Sensorless
voltage
compensation1
SL Volt
Comp1
0-60
Depend
ent on
motor
setting
O/A X
I
p.150
92
42
0h145C
Sensorless
voltage
compensation2
SL Volt
Comp2
0-60
O/A X
I
p.150
93
42
0h145D
Sensorless
voltage
compensation3
SL Volt
Comp3
0-60
O/A X
I
p.150
94
42
0h145E
Sensorless field
weakening start
frequency
SL FW Freq 80.0-110.0(%)
100.0
X/A
X
I
p.146
41
Displayed when Cn.77 is not set to 0 (No).
42
Displayed when Cn.20 is set to 1 (Yes).
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......