Local/Remote Mode Switching Setting Details
Code
Description
dr.90
[ESC] key functions
Set dr.90 to 2(Local/Remote) to perform local/remote switching using the [ESC]
key. Once the value is set, the inverter will automatically begin operating in remote
mode. Changing from local to remote will not alter any previously configured
parameter values and the operation of the inverter will not change.
Press the [ESC] key to switch the operation mode back to “local.” The SET light will
flash, and the inverter will operate using the [RUN] key on the keypad. Press the
[ESC] key again to switch the operation mode back to “remote.” The SET light will
turn off and the inverter will operate according to the previous drv code
configuration.
Note
Local/Remote Operation
•
Full control of the inverter is available with the keypad during local operation.
•
During local operation, jog commands will only work if one of the P1–P5 multi-function terminals
(codes In.65–69) is set to 13(RUN Enable) and the relevant terminal is turned on.
•
During remote operation (remote operation), the inverter will operate according to the previously
set frequency reference source and the command received from the input device.
•
If Ad.10 (power-on run) is set to 0(No), the inverter will NOT operate on power-on even when the
following terminals are turned on:
- Fwd/Rev run (Fx/Rx) terminal
- Fwd/Rev jog terminal (Fwd jog/Rev Jog)
- Pre-Excitation terminal
To operate the inverter manually with the keypad, switch to local mode. Use caution when
switching back to remote operation mode as the inverter will stop operating. If Ad.10 (power-on
run) is set to 0(No), a command through the input terminals will work ONLY AFTER all the
terminals listed above have been turned off and then turned on again.
•
If the inverter has been reset to clear a fault during an operation, the inverter will switch to local
operation mode at power-on, and full control of the inverter will be with the keypad. The inverter
will stop operating when operation mode is switched from “local” to “remote”. In this case, a run
command through an input terminal will work ONLY AFTER all the input terminals have been
turned off.
Inverter Operation During Local/Remote Switching
Switching operation mode from “remote” to “local” while the inverter is running will cause the inverter
to stop operating. Switching operation mode from “local” to “remote” however, will cause the inverter
to operate based on the command source:
•
Analog commands via terminal input: the inverter will continue to run without interruption based
on the command at the terminal block. If a reverse operation (Rx) signal is ON at the terminal
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......