Learning Advanced Features
176
Note
•
If operated within the rated output, the ”S” Series inverter is designed to withstand instantaneous
power interruptions within 15 ms and maintain normal operation. Based on the rated heavy load
current, safe operation during an instantaneous power interruption is guaranteed for 200V and
400V inverters (whose rated input voltages are 200-240 VAC and 380-480 VAC respectively).
•
The DC voltage inside the inverter may vary depending on the output load. If the power
interruption time is longer than 15 ms, a low voltage trip may occur.
When operating in sensorless II mode while the load is spinning, the speed search function (for general
acceleration) must be set for smooth operation. If the speed search function is not set, an overcurrent
trip or overload trip may occur.
Auto Restart Settings
When inverter operation stops due to a fault, the inverter automatically restarts based on the
parameter settings.
Group
Code
Name
LCD Display
Parameter Setting Setting Range Unit
Pr
08
Select start at trip
reset
RST Restart
0
No
0–1
-
09
Auto restart count
Retry
Number
0
0–10
-
10
Auto restart delay
time
Retry Delay
1.0
0.0–60.0
s
Cn
71
Select speed
search operation
Speed Search -
0000*
–
1111
bit
72
Speed search
startup current
SS Sup-
Current
150
80
–
200
%
73
Speed search
proportional gain
SS P-Gain
100
0
–
9999
74
Speed search
integral gain
SS I-Gain
200
0
–
9999
75
Output block time
before speed
search.
SS Block
Time
1.0
0.0
–
60.0
s
*Displayed as
on the keypad.
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......