RS-485 Communication Features
252
Comm. Address
Parameter
Scale
Unit
Assigned Content by Bit
0h038C-
0h038F
Reserved
-
0h0390
Torque Ref
0.1
%
Torque command
0h0391
Fwd Pos
Torque Limit
0.1
%
Forward motoring torque limit
0h0392
Fwd Neg
Torque Limit
0.1
%
Forward regenerative torque limit
0h0393
Rev Pos
Torque Limit
0.1
%
Reverse motoring torque limit
0h0394
Rev Neg
Torque Limit
0.1
%
Reverse regenerative torque limit
0h0395
Torque Bias
0.1
%
Torque bias
0h0396- 0h399
Reserved
-
-
-
0h039A
Anytime Para -
-
Set the CNF.20
*
value (refer to 5.37
on page
207)
0h039B
Monitor Line-
1
-
-
Set the CNF.21
*
value (refer to 5.37
on page
207)
0h039C
Monitor Line-
2
-
-
Set the CNF.22
*
value (refer to 5.37
on page
207)
0h039D
Monitor Line-
3
-
-
Set the CNF.23
*
value (refer to 5.37
on page
207)
*
Displayed on an LCD keypad only.
Note
A frequency set via communication using the common area frequency address (0h0380, 0h0005) is not
saved even when used with the parameter save function. To save a changed frequency to use after a
power cycle, follow these steps:
1
Set dr.07 to Keypad-1 and select a random target frequency.
2
Set the frequency via communication into the parameter area frequency address (0h1101).
3
Perform the parameter save (0h03E0: '1') before turning off the power. After the power cycle, the
frequency set before turning off the power is displayed.
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......