Learning Advanced Features
206
Code
Description
On Dly,
OU.54 TripOut
OffDly
OU.53. Terminal is reset (opened) when the fault is reset after the time delay set in
OU.53.
Multi-function Output Terminal Delay Time Settings
Set on-delay and off-delay times separately to control the Q1 output terminal and relay operation
times. The delay time set at codes OU.50
–
51 applies to multi-function output terminal (Q1) and
relay (Relay 1), except when the multi-function output function is in a fault mode.
Output Terminal Delay Time Setting Details
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
OU
50
Multi-
function
output On
delay
DO On
Delay
0.00
0.00
–
100.00 s
51
Multi-
function
output Off
delay
DO Off
Delay
0.00
0.00
–
100.00 s
52
Select
multi-
function
output
terminal
DO NC/NO
Sel
00*
00
–
11
bit
* Displayed as
on keypad.
OU 50. DO On Delay
OU 51. DO Off Delay
Run cmd
Multi-function
output