Learning Protection Features
Group
Code
Name
LCD Display
Parameter
Setting
Setting range
Unit
55
Stall
frequency 3
Stall Freq 3
60.00
Stall Freq 2–Stall
Freq 4
Hz
56
Stall level 3
Stall Level 3
180
30-250
%
57
Stall
frequency 4
Stall Freq 4
60.00
Stall Freq 3–
Maximum
frequency
Hz
58
Stall level 4
Stall Level 4
180
30-250
%
OU
31
Multi-function
relay 1 item
Relay 1
9 Stall
-
-
33
Multi-function
output 1 item
Q1 Define
* The value is displayed on the keypad as
.
Stall Prevention Function and Flux Braking Setting Details
Code
Description
Pr.50 Stall
Prevent
Stall prevention can be configured for acceleration, deceleration, or while operating a
motor at constant speed. When the top LED/LCD segment is on, the corresponding bit
is set On (or 1). When the bottom LED/LCD segment is on, the corresponding bit is set
Off (or 0).
Item
Bit Status (On)
Bit Status (Off)
Keypad
LCD keypad
Setting
Function
Bit 4
Bit 3
Bit 2
Bit 1
Stall protection during acceleration
Stall protection while operating at a
constant speed
Stall protection during deceleration
Flux braking during deceleration
Setting
Function
0001
Stall protection
during
acceleration
If inverter output current exceeds the preset
stall levels (Pr. 52, 54, 56, 58) during
acceleration, the motor stops accelerating
and starts decelerating. If current level stays
above the stall level, the motor decelerates to
the start frequency (dr.19). If the current level
drops below the preset level while operating
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......