Learning Advanced Features
137
PID Basic Operation Setting Details
Code
Description
AP.01 App Mode
Set the code to 2 (Proc PID) to select functions for the process PID.
AP.16 PID Output
Displays the existing output value of the PID controller. The unit, gain, and
scale that were set at AP. 42-44 are applied on the display.
AP.17 PID Ref Value
Displays the existing value of the PID controller reference (setpoint) source.
The unit, gain, and scale that were set at AP. 42-44 are applied on the
display.
AP.18 PID Fdb Value Displays the existing value of the PID controller feedback source. The unit,
gain, and scale that were set at AP. 42-44 are applied on the display.
AP.19 PID Ref Set
When AP.20 (PID control reference source) is set to 0 (Keypad), the reference
value can be entered. If the reference source is set to any other value, the
setting values for AP.19 are void.
AP.20 PID Ref Source Selects the source of the reference (setpoint) input for PID control. The
reference (setpoint) source cannot be the same source as the PID feedback
source (PID F/B Source).
Setting
Function
0
Keypad
Keypad
1
V1
-10-10V input voltage terminal
3
V2
I2 analog input terminal
[When analog voltage/current input switch (SW2) at the
terminal block is set to I (current), input 4-20mA current. If it
is set to V (voltage), input 0–10V voltage]
4
I2
5
Int. 485
RS-485 input terminal
7
FieldBu
s
Communication command via a communication option card
9
UserSe
qLink
Link the common area with the user sequence output.
11
Pulse
TI Pulse input terminal (0-32kHz Pulse input)
When using the 7-segment keypad, the PID reference setting can be
displayed at AP.17. When using the LCD keypad, the PID reference setting
can be viewed in the Monitor Mode by assigning config mode parameters
(CNF).21-23, set to 17 (PID Ref Value).
AP.21 PID F/B Source Selects the source of the feedback input to the PID control. The same list of
sources (above) can be selected, except the keypad input (Keypad-1 and
Keypad-2). Also, the feedback source cannot be the same as the reference
(setpoint) source. When using the LCD keypad, the feedback can be viewed
in the Monitor Mode by assigning config mode parameters (CNF).21-23, set
to 18 (PID Fbk Value).
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......