Learning Advanced Features
98
Code
Description
Freq
inverter output is cut off. After the block time [Ad.14], the inverter applies DC
power to the motor for the time set in Ad.15. If there is a dwell frequency set
[Ad.22, Ad.23] lower than the DC braking frequency, dwell operation will be
ignored and DC braking will start instead.
•
Note that the motor can overheat or be damaged if excessive amount of DC braking is applied to
the motor, or DC braking time is set too long.
•
DC braking is configured based on the motor’s rated current. To prevent overheating or damaging
motors, do not set the current value higher than the inverter’s rated current.
Free Run Stop
When the run command is turned off, the inverter output turns off and the motor/load coasts to a
stop due to residual inertia.
Group Code Name
LCD Display
Parameter Setting Setting Range
Unit
Ad
08
Stop Method
Stop Mode
2
Free-Run 0
–
4
-
Ad.17
Ad.14 Ad.15
Ad.16
Frequency
Voltage
Current
Run cmd
Frequency,
voltage
Run cmd