Learning Advanced Features
202
Code
Description
2
FDT-2
FDT-2 compares the reference frequency to the
detect frequency OU.57, FDT frequency. Relay1 (or
Q1) closes when the reference frequency and the
detect frequency are within ½ of the FDT Band,
OU.58.
Eq:
[Absolute value (set frequency-detected
frequency) < detected frequency width/2]&[FDT-1]
Ex:
OU.57, FDT Frequency = 30 Hz.
OU.58, FDT Band = 10 Hz.
FDT-2 functions as shown in the graph below.
3
FDT-3
FDT-3 compares the output frequency to the detect
frequency OU.57, FDT Frequency. Relay1 (or Q1)
closes when the output frequency and the detect
frequency OU.57 are within ½ the FDT Band, OU.58.
Eq:
Absolute value (output frequency
–
operation
frequency) < detected frequency width/2.
Ex:
OU.57, FDT Frequency = 30 Hz.
OU.58, FDT Band = 10 Hz.
FDT-3 functions as shown in the graph below.
4
FDT-4
FDT-4 compares the output frequency to the detect
frequency OU.57, FDT Frequency. Relay1 (or Q1)
closes when the output frequency reaches the detect
frequency OU.57, FDT Frequency and remains closed
above the detect frequency (does not consider the
FDT Band frequency). During deceleration, Relay1 (or
Q1) closes when the output frequency reaches the
detect frequency OU.57, FDT Frequency and is below
½ the FDT Band, OU.58.
Q1
25Hz
30Hz
50Hz
Frequency
reference
Frequency
Run cmd
30Hz
35Hz
25Hz
Q1
Frequency
Run cmd
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......