Learning Advanced Features
52
Note
The instructions in the table are based on the factory default parameter settings. The inverter may not
work correctly if the default parameter settings are changed after the inverter is purchased. In such
cases, initialize all parameters to reset the values to factory default parameter settings before following
the instructions in the table (refer to 5.23).
Frequency Setting (Potentiometer) and Operation (Terminal
Input)
Step
Instruction
Keypad Display
1
Turn on the inverter.
-
2
Ensure that the first code of the Operation group is selected,
and the code 0.00 (Command Frequency) is displayed.
3
Press the [
▲
] key 4 times to go to the Frq (Frequency reference
source) code.
4
Press the [ENT] key.
The Frq code in the Operation group is currently set to 0
(keypad).
5
Press the [
▲
] key to change the parameter value to 2
(Potentiometer), and then press the [ENT] key.
The new parameter value will flash.
6
Press the [ENT] key once again.
The Frq code will be displayed again. The frequency input has
been configured for the potentiometer.
7
Press the [
▼
] key 4 times.
Returns to the first code of the Operation group (0.00).From
here frequency setting values can be monitored.
8
Adjust the potentiometer to verify the frequency reference
changes. The frequency reference will change eventhough
the drive is not running yet.
-
9
Refer to the wiring diagram at the bottom of the table, and
close the switch between the P1 (FX) and CM terminals.
The FWD indicator light comes on steady. The RUN indicator
light flashes as the drive accelerates from 0 Hz. to the
frequency reference. When the drive frequency is reached,
the RUN indicator light becomes steady (not flashing).
10
When the frequency reference is reached (10Hz), open the
switch between the P1 (FX) and CM terminals.
The RUN indicator light flashes again and the decelerating
frequency is displayed. When the frequency reaches 0Hz, the
RUN and FWD indicators turn off, and the frequency reference
is displayed again.
SET
RUN
FWD
REV
10.00
SET
RUN
FWD
REV
10.00
0.00
Frq
0
‘2’
Frq
0.00
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......