Learning Advanced Features
144
Auto Tuning Default Parameter Setting
Motor Capacity
(kW)
Rated
Current (A)
No-load
Current
(A)
Rated Slip
Frequency(Hz)
Stator
Resistance(
Ω
Ω
Ω
Ω
)
Leakage
Inductance (mH)
200V
0.2
1.1
0.8
3.33
14.0
40.4
0.4
2.4
1.4
3.33
6.70
26.9
0.75
3.4
1.7
3.00
2.600
17.94
1.5
6.4
2.6
2.67
1.170
9.29
2.2
8.6
3.3
2.33
0.840
6.63
3.7
13.8
5.0
2.33
0.500
4.48
5.5
21.0
7.1
1.50
0.314
3.19
7.5
28.2
9.3
1.33
0.169
2.844
11
40.0
12.4
1.00
0.120
1.488
15
53.6
15.5
1.00
0.084
1.118
18.5
65.6
19.0
1.00
0.068
0.819
22
76.8
21.5
1.00
0.056
0.948
400V
0.2
0.7
0.5
3.33
28.00
121.2
0.4
1.4
0.8
3.33
14.0
80.8
0.75
2.0
1.0
3.00
7.81
53.9
1.5
3.7
1.5
2.67
3.52
27.9
2.2
5.0
1.9
2.33
2.520
19.95
3.7
8.0
2.9
2.33
1.500
13.45
5.5
12.1
4.1
1.50
0.940
9.62
7.5
16.3
5.4
1.33
0.520
8.53
11
23.2
7.2
1.00
0.360
4.48
15
31.0
9.0
1.00
0.250
3.38
18.5
38.0
11.0
1.00
0.168
2.457
22
44.5
12.5
1.00
0.168
2.844
*When Dr.09 (Control Mode) is set to 6 (PM Sensorless), auto tuning will configure the rated current
and the stator resistor values by default.
Auto Tuning Parameter Setting Details
Code
Description
bA.20 Auto Tuning
Select an auto tuning type then press the [ENT] key to run the auto tuning.
Setting
Function
0
None
Auto tuning function is not enabled. Note: when
you select one of the auto tuning options below
and run it, this parameter value will revert back to
“0” when the auto tuning is complete.
1
All (rotating
type)
Measures all motor parameters, including stator
resistance (Rs), stator inductance (Lsigma), no-
load current (Noload Curr), rotor time constant
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......