Learning Advanced Features
190
Code
Description
the LCD keypad to the inverter updates titles.
CNF-62 WH Count Reset
Initialize kWH (accumulated electric energy consumption).
Timer Settings
Set a digital input terminal to activate a timer to control the multi-function outputs (Relay1 or Q1)
according to the timer settings.
Group
Code
Name
LCD Display
Parameter Setting Setting Range Unit
In
65–69
Px terminal
configuration
Px Define(Px:
P1–P5)
38
Timer In
-
-
OU
31
Multi-function
relay1
Relay 1
28
Timer Out -
-
33
Multi-function
output1
Q1 Define
55
Timer on delay
Timer on delay 3.00
0.00–100
sec
56
Timer off delay
Timer off delay 1.00
0.00–100
sec
Timer Setting Details
Code
Description
In.65
–
71 Px Define
Choose one of the digital input terminals and change it to a timer input
terminal by setting it to 38 (Timer In).
OU.31 Relay1,
OU.33 Q1 Define
Set either one of the multi-function outputs (Relay1 or Q1) to 28 (Timer out).
OU.55 TimerOn Delay,
OU.56 TimerOff Delay
Configure the On delay and Off delay settings of the multi-function output.
When the digital input terminal is activated to operate the timer, the multi-
function output will close after the time set at OU.55 has passed. When the
digital input terminal is de-activated (opened), the multi-function output opens
after the time set at OU.56.
Px(Timer In)
Q
1(Timer Out)
OU.55
OU.56
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......