Learning Advanced Features
100
Frequency Limit
Operation frequency can be limited by setting the start frequency, maximum frequency, upper limit
frequency and lower limit frequency.
Frequency Limit Using Maximum Frequency and Start Frequency
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
dr
19
Start frequency
Start Freq
0.50
0.01
–
10.00
Hz
20
Maximum frequency Max Freq
60.00
40.00
–
400.00
Hz
Frequency Limit Using Maximum Frequency and Start Frequency - Setting Details
Code
Description
dr.19 Start Freq
Set the lower limit value for speed unit parameters that are expressed in Hz or
rpm. If an input frequency is lower than the start frequency, the displayed value
will be 0.00.
dr.20 Max Freq
Set a maximum frequency for all speed unit parameters that are expressed in Hz
or rpm, except for the base frequency (dr.18). Frequency cannot be set higher
than the maximum frequency.
Frequency Limit Using Upper and Lower Limit Frequency Values
Group Code
Name
LCD Display
Parameter Setting Setting Range
Unit
Ad
24
Frequency limit
Freq Limit
0
No
0–1
-
1
Yes
25
Frequency lower limit
value
Freq Limit Lo 0.50
0.0
–
maximum
frequency
Hz
26
Frequency upper limit
value
Freq Limit Hi
Maximum
frequency
minimum
–
maximum
frequency
Hz
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......