Learning Advanced Features
78
Fwd/Rev Command by Multi-function Terminal – Setting Details
Code
Description
Operation group
drv– Cmd Source
Set to 1(Fx/Rx-1).
In.65–71 Px Define
Assign a terminal for forward (Fx) operation.
Assign a terminal for reverse (Rx) operation.
Terminal Block as a Command Input Device (Run and Rotation
Direction Commands)
The digital inputs can be selected to operate as the start/stop source along with direction of
rotation. This is configured by setting the drv (command source) code in the Operation group to
2(Fx/Rx-2). Select 2 terminals for run and rotation direction commands, codes In.65
–
69 for P1
–
P5
to 1(Fx) and 2(Rx) respectively. This application uses the Fx input as a run command while the Rx
input determines the motor’s rotation direction.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
Operation
Drv
Command
source
Cmd
Source*
2 Fx/Rx-2
0
–
5
-
In
65
–
69
Px terminal
configuration
Px Define
(Px: P1 – P5)
1
Fx
0
–
54
-
2 Rx
* Displayed under DRV-06 on the LCD keypad.
Run Command and Fwd/Rev Change Command Using Multi-function Terminal – Setting Details
Code
Description
Operation group
drv Cmd Source
Set to 2(Fx/Rx-2).
In.65–71 Px Define
Assign a terminal for run command (Fx).
Assign a terminal for changing rotation direction (Rx).
FX
RX
Frequency reference
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......