Learning Advanced Features
177
Auto Restart Setting Details
Code
Description
Pr.08 RST Restart,
Pr.09 Retry Number,
Pr.10 Retry Delay
Only operates when Pr.08 (RST Restart) is set to 1(Yes). The number of
attempts to try the auto restart is set at Pr.09 (Auto Restart Count).
If a fault occurs during normal operation, the inverter automatically restarts
after the set time programmed at Pr.10 (Retry Delay). At each restart, the
inverter counts the number of tries and subtracts it from the number set at
Pr.09 until the retry number count reaches 0.
After an auto restart, if a fault does not occur within 60 sec, it will increase the
restart count number. The maximum count number is limited by the number
set at Pr.09 (Auto Restart Count).
If the inverter stops due to low voltage, emergency stop (Bx), inverter
overheating, or hardware diagnosis, an auto restart is not activated. At auto
restart, the acceleration options are identical to those of speed search
operation. Codes Cn.72
–
75 can be set based on the load. Information about
the speed search function can be found at 5.15
.
[Example of auto restart with a setting of 2]
If the auto restart number is set, be careful when the inverter resets a fault, the motor may
automatically start to rotate.
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......