Learning Advanced Features
183
Group
Code
Name
LCD Display
Parameter Setting
Setting Range Unit
bA
19
Input power
voltage
AC Input Volt
240V
240
170–240
V
480V
480
320–480
Read, Write, and Save Parameters
Use read, write and save function parameters on the inverter to copy parameters from the inverter
to the keypad or from the keypad to the inverter.
Group
Code
Name
LCD Display
Parameter Setting Setting Range Unit
CNF*
46
Parameter read
Parameter Read 1
Yes
-
-
47
Parameter write
Parameter
Write
1
Yes
-
-
48
Parameter save
Parameter Save 1
Yes
-
-
*Available on LCD keypad only.
Read, Write, and Save Parameter Setting Details
Code
Description
CNF-46
Parameter Read
Copies saved parameters from the inverter to the keypad. Saved parameters on
the keypad will be deleted and replaced with copied parameters.
CNF-47
Parameter Write
Copies saved parameters from the keypad to the inverter. Saved parameters on
the inverter will be deleted and replaced with copied parameters. If an error occurs
during parameter writing, previous saved data will be used. If there is no saved data
on the Keypad,
‘
EEP Rom Empty
’
message will be displayed.
CNF-48
Parameter Save
As parameters set during communication transmission are saved to RAM, the
setting values will be lost if the power goes off and on. When setting parameters
during communication transmission, select 1 (Yes) from CNF-48 code to save the
set parameter.
Parameter Initialization
User changes to parameters can be initialized (reset) to factory default settings on all or selected
groups. However, during a fault or during operation, parameters cannot be initialized.
Group
Code
Name
LCD Display
Parameter
Setting
Setting
Range
Unit
dr*
93
Parameter
initialization
-
0
No
0
–
16
CNF**
40
Parameter
initialization
Parameter
Init
0
No
0
–
16
* For keypad
**For LCD keypad
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......