Learning Advanced Features
134
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range Unit
dr
09
Control mode
Control Mode
2 Slip
Compen
-
-
14
Motor capacity Motor Capacity
2 0.75 kW
0-15
-
bA
11
Number of
motor poles
Pole Number
4
2-48
-
12
Rated slip
speed
Rated Slip
90
0-3000
rpm
13
Rated motor
current
Rated Curr
3.6
1.0-1000.0
A
14
Motor no-load
current
Noload Curr
1.6
0.5-1000.0
A
16
Motor
efficiency
Efficiency
72
64-100
%
17
Load inertia
rate
Inertia Rate
0
0-8
-
Slip Compensation Operation Setting Details
Code
Description
dr.09 Control Mode
Set dr.09 to 2 (Slip Compen) to carry out the slip compensation operation.
dr.14 Motor Capacity Set the capacity of the motor connected to the inverter.
bA.11 Pole Number
Enter the number of poles from the motor rating plate.
bA.12 Rated Slip
Enter the number of rated rotations from the motor rating plate.
bA.13 Rated Curr
Enter the rated current from the motor rating plate.
bA.14 Noload Curr
Enter the measured current when the load on the motor axis is removed and
when the motor is operated at the rated frequency. If no-load current is difficult
to measure, enter a current equivalent to 30-50% of the rated motor current.
bA.16 Efficiency
Enter the efficiency from the motor rating place.
bA.17 Inertia Rate
Select load inertia based on motor inertia.
Setting
Function
0
Less than 10 times motor inertia
1
10 times motor inertia
2-8
More than 10 times motor inertia
=
−
×
120
=Rated slip frequency
=Rated frequency
=Number of the rated motor rotations
=Number of motor poles
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......