Learning Protection Features
Group
Code
Name
LCD Display
Parameter Setting Setting
range
Unit
33
No motor
detection time
No Motor
Time
3.0
0.1-10
s
No Motor Trip Setting Details
Code
Description
Pr.32 No Motor
Level, Pr.33 No
Motor Time
If the output current value [based on the rated current (bA.13)] is lower than the
value set at Pr.32 (No Motor Level), and if this continues for the time set at Pr.33
(No Motor Time), a ‘no motor trip’ occurs.
If bA.07 (V/F Pattern) is set to 1 (Square), set Pr.32 (No Motor Level) to a value lower than the factory
default. Otherwise, ‘no motor trip’ due to a lack of output current will result when the ‘no motor trip’
operation is set.
Low voltage trip 2
If you set the Pr-82(LV2 Selection) code to Yes (1), this changes the low voltage fault to a latched
fault and the fault notification is displayed. Reset the inverter to clear the fault. The trip history will
not be saved.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
Pr
82
LV2 Selection
LV2 Enable
Yes(1)
0/1
-