Learning Advanced Features
131
Safe Operation Mode Setting Details
Code
Description
In.65–69 Px Define
From the multi-function terminals, select a terminal to operate in safe
operation mode and set it to 13 (RUN Enable).
In.60 Run En Mode
Setting
Function
0
Always Enable
Enables safe operation mode.
1
DI Dependent
Recognizes the operation command from a
digital input terminal.
In.61 Run Dis Stop
When the inverter is running, set the operation of the inverter when the
digital input terminal set to Run Enable is opened.
Setting
Function
1
Free-Run
Blocks the inverter output when the digital
input terminal is open. Coast to stop.
2
Q-Stop
The deceleration time (In.62, Q-Stop Time) is
used and the inverter stops after deceleration.
Operation can resume only when the run
enable input along with the opertation
command (Fx) is appled again. The operation
will not begin if only the Run enable input is
applied.
3
Q-Stop
Resume
The deceleration time (IN.62, Q-Stop Time) is
used and the inverter decelerates. If the Run
enable input is re-appled, the operation
resumes.
In.62 Q-Stop Time
Sets the deceleration time when In.61 (Run Dis Stop) is set to 1 (Q-Stop) or 2
(Q-Stop Resume).
In.61
In.61
In.61
Содержание Rsi S Series
Страница 2: ......
Страница 6: ......
Страница 12: ...Preparing the Installation 0...
Страница 22: ...Preparing the Installation 10...
Страница 70: ...LearningAdvanced Features 58...
Страница 152: ...LearningAdvanced Features 140 PID controlblock diagram...
Страница 224: ...LearningAdvanced Features 212...
Страница 356: ...344...
Страница 362: ...Maintenance 350...
Страница 381: ...369 TechnicalSpecification...
Страница 397: ......